PoEswitch EN: Różnice pomiędzy wersjami
(→1. STATUS) |
(→SNMP OID NUMBERS) |
||
(Nie pokazano 1 pośredniej wersji utworzonej przez tego samego użytkownika) | |||
Linia 83: | Linia 83: | ||
INP2D State – shows the status of the input INP2D. | INP2D State – shows the status of the input INP2D. | ||
Out_T on/off – shows the status of output Out_T. | Out_T on/off – shows the status of output Out_T. | ||
− | + | ||
− | + | ===POE=== | |
− | + | ||
− | + | zdjecie | |
− | + | ||
+ | ===PORTS=== | ||
any description | any description | ||
max 8 characters | max 8 characters | ||
Linia 102: | Linia 103: | ||
Power on the PoE port | Power on the PoE port | ||
after reboot / start switch | after reboot / start switch | ||
− | + | ||
− | + | ===VLAN=== | |
− | |||
− | |||
Inclusion of of isolation between ports: | Inclusion of of isolation between ports: | ||
In order to isolate traffic between the ports, so that the traffic was directed only to the | In order to isolate traffic between the ports, so that the traffic was directed only to the | ||
Linia 113: | Linia 112: | ||
from each port) and port „5”. For the port „5” we leave all selections (except P5). Then | from each port) and port „5”. For the port „5” we leave all selections (except P5). Then | ||
memorize the setting with „Save” button. | memorize the setting with „Save” button. | ||
− | + | ||
− | + | ===WATCHDOG=== | |
− | |||
− | |||
Email send – sends an e-mail when the watchdog work (will restart power supply on | Email send – sends an e-mail when the watchdog work (will restart power supply on | ||
a port PoE). E-mail contains information about the number of the current restart and | a port PoE). E-mail contains information about the number of the current restart and | ||
Linia 133: | Linia 130: | ||
restartować urządzenia, które i tak nie ma zamiaru poprawnie pracować. | restartować urządzenia, które i tak nie ma zamiaru poprawnie pracować. | ||
POE state – determines the state of power supply to PoE port: red OFF, green ON. | POE state – determines the state of power supply to PoE port: red OFF, green ON. | ||
− | + | ||
− | + | ||
− | + | ===SWITCH SETTINGS=== | |
− | + | The user name and | |
− | The user name and | + | password to access |
− | password to access | ||
the module. | the module. | ||
You can disable | You can disable | ||
Linia 149: | Linia 145: | ||
network settings | network settings | ||
configuration. | configuration. | ||
− | + | ||
− | + | ---- | |
− | |||
Configure email | Configure email | ||
account to send | account to send | ||
Linia 159: | Linia 154: | ||
in software upgrade mode | in software upgrade mode | ||
Password for SNMP | Password for SNMP | ||
− | + | ||
− | + | ==Software update== | |
− | |||
− | Software update | ||
In the event that there is a new version of the software it is possible to load such software | In the event that there is a new version of the software it is possible to load such software | ||
for the device. | for the device. | ||
+ | |||
To install the new firmware to the switch should move it in bootloader mode. The easiest | To install the new firmware to the switch should move it in bootloader mode. The easiest | ||
− | way to do it from the menu Switch Settings/Others: | + | way to do it from the menu '''Switch Settings/Others''': |
− | 1. the | + | |
+ | 1. the „'''Upgrade Enabled'''” in the Switch Settings / Access must be enabled. | ||
2. through the „Bootloader start” button. | 2. through the „Bootloader start” button. | ||
We have 60 seconds to start uploading via FTP. This will take about 6÷7 seconds and after | We have 60 seconds to start uploading via FTP. This will take about 6÷7 seconds and after | ||
Linia 184: | Linia 179: | ||
Copying, duplication, reproduction whole or in part | Copying, duplication, reproduction whole or in part | ||
without the consent of the owner is prohibited. | without the consent of the owner is prohibited. | ||
− | + | ||
− | + | ==SNMP OID NUMBERS== | |
− | + | ===A group of voltages, currents, inputs, PoE=== | |
− | SNMP OID NUMBERS | + | iso.3.6.1.4.1.7616.1.1.0 = INTEGER: 125 – supply voltage, divide the result by 10 <br/> |
− | A group of voltages, currents, inputs, PoE | + | iso.3.6.1.4.1.7616.1.1.1 = INTEGER: 0 – INP1A, voltage, divide the result by 10 <br/> |
− | iso.3.6.1.4.1.7616.1.1.0 = INTEGER: 125 – supply voltage, divide the result by 10 | + | iso.3.6.1.4.1.7616.1.1.2 = INTEGER: 387 – temperature, divide the result by 10 <br/> |
− | iso.3.6.1.4.1.7616.1.1.1 = INTEGER: 0 – INP1A, voltage, divide the result by 10 | + | iso.3.6.1.4.1.7616.1.1.3 = INTEGER: 1 – INP1D <br/> |
− | iso.3.6.1.4.1.7616.1.1.2 = INTEGER: 387 – temperature, divide the result by 10 | + | iso.3.6.1.4.1.7616.1.1.4 = INTEGER: 1 – INP2D <br/> |
− | iso.3.6.1.4.1.7616.1.1.3 = INTEGER: 1 – INP1D | + | iso.3.6.1.4.1.7616.1.2.0 = INTEGER: 1 – PoE port1 ON/OFF <br/> |
− | iso.3.6.1.4.1.7616.1.1.4 = INTEGER: 1 – INP2D | + | iso.3.6.1.4.1.7616.1.2.1 = INTEGER: 1 – PoE port2 ON/OFF <br/> |
− | iso.3.6.1.4.1.7616.1.2.0 = INTEGER: 1 – PoE port1 ON/OFF | + | iso.3.6.1.4.1.7616.1.2.2 = INTEGER: 1 – PoE port3 ON/OFF <br/> |
− | iso.3.6.1.4.1.7616.1.2.1 = INTEGER: 1 – PoE port2 ON/OFF | + | iso.3.6.1.4.1.7616.1.2.3 = INTEGER: 1 – PoE port4 ON/OFF <br/> |
− | iso.3.6.1.4.1.7616.1.2.2 = INTEGER: 1 – PoE port3 ON/OFF | + | iso.3.6.1.4.1.7616.1.2.4 = INTEGER: 0 – PoE OUT_T ON/OFF <br/> |
− | iso.3.6.1.4.1.7616.1.2.3 = INTEGER: 1 – PoE port4 ON/OFF | + | iso.3.6.1.4.1.7616.1.3.0 = INTEGER: 0 – PoE port1 current mA <br/> |
− | iso.3.6.1.4.1.7616.1.2.4 = INTEGER: 0 – PoE OUT_T ON/OFF | + | iso.3.6.1.4.1.7616.1.3.1 = INTEGER: 21 – PoE port2 current mA <br/> |
− | iso.3.6.1.4.1.7616.1.3.0 = INTEGER: 0 – PoE port1 current mA | + | iso.3.6.1.4.1.7616.1.3.2 = INTEGER: 53 – PoE port3 current mA <br/> |
− | iso.3.6.1.4.1.7616.1.3.1 = INTEGER: 21 – PoE port2 current mA | + | iso.3.6.1.4.1.7616.1.3.3 = INTEGER: 0 – PoE port4 current mA <br/> |
− | iso.3.6.1.4.1.7616.1.3.2 = INTEGER: 53 – PoE port3 current mA | + | iso.3.6.1.4.1.7616.1.3.4 = INTEGER: 74 – PoE the sum of currents from p1 to p4 mA <br/> |
− | iso.3.6.1.4.1.7616.1.3.3 = INTEGER: 0 – PoE port4 current mA | + | iso.3.6.1.4.1.7616.1.4.0 = INTEGER: 0 – PoE port1 power mW <br/> |
− | iso.3.6.1.4.1.7616.1.3.4 = INTEGER: 74 – PoE the sum of currents from p1 to p4 mA | + | iso.3.6.1.4.1.7616.1.4.1 = INTEGER: 262 – PoE port2 power mW <br/> |
− | iso.3.6.1.4.1.7616.1.4.0 = INTEGER: 0 – PoE port1 power mW | + | iso.3.6.1.4.1.7616.1.4.2 = INTEGER: 662 – PoE port3 power mW <br/> |
− | iso.3.6.1.4.1.7616.1.4.1 = INTEGER: 262 – PoE port2 power mW | + | iso.3.6.1.4.1.7616.1.4.3 = INTEGER: 0 – PoE port4 power mW <br/> |
− | iso.3.6.1.4.1.7616.1.4.2 = INTEGER: 662 – PoE port3 power mW | + | iso.3.6.1.4.1.7616.1.4.4 = INTEGER: 925 – PoE the sum of power from p1 to p4 mW <br/> |
− | iso.3.6.1.4.1.7616.1.4.3 = INTEGER: 0 – PoE port4 power mW | + | iso.3.6.1.4.1.7616.2.1.0 = INTEGER: 1 – Port1 On/OFF <br/> |
− | iso.3.6.1.4.1.7616.1.4.4 = INTEGER: 925 – PoE the sum of power from p1 to p4 mW | + | iso.3.6.1.4.1.7616.2.1.1 = INTEGER: 1 – Port2 On/OFF <br/> |
− | + | iso.3.6.1.4.1.7616.2.1.2 = INTEGER: 1 – Port3 On/OFF <br/> | |
− | + | iso.3.6.1.4.1.7616.2.1.3 = INTEGER: 1 – Port4 On/OFF <br/> | |
− | + | iso.3.6.1.4.1.7616.2.1.4 = INTEGER: 1 – Port5 On/OFF <br/> | |
− | iso.3.6.1.4.1.7616.2.1.0 = INTEGER: 1 – Port1 On/OFF | + | iso.3.6.1.4.1.7616.2.2.0 = INTEGER: 0 – Port1 link <br/> |
− | iso.3.6.1.4.1.7616.2.1.1 = INTEGER: 1 – Port2 On/OFF | + | iso.3.6.1.4.1.7616.2.2.1 = INTEGER: 1 – Port2 link <br/> |
− | iso.3.6.1.4.1.7616.2.1.2 = INTEGER: 1 – Port3 On/OFF | + | iso.3.6.1.4.1.7616.2.2.2 = INTEGER: 1 – Port3 link <br/> |
− | iso.3.6.1.4.1.7616.2.1.3 = INTEGER: 1 – Port4 On/OFF | + | iso.3.6.1.4.1.7616.2.2.3 = INTEGER: 1 – Port4 link <br/> |
− | iso.3.6.1.4.1.7616.2.1.4 = INTEGER: 1 – Port5 On/OFF | + | iso.3.6.1.4.1.7616.2.2.4 = INTEGER: 1 – Port5 link <br/> |
− | iso.3.6.1.4.1.7616.2.2.0 = INTEGER: 0 – Port1 link | + | iso.3.6.1.4.1.7616.2.3.0 = INTEGER: 10 – Port1 speed <br/> |
− | iso.3.6.1.4.1.7616.2.2.1 = INTEGER: 1 – Port2 link | + | iso.3.6.1.4.1.7616.2.3.1 = INTEGER: 100 – Port2 speed <br/> |
− | iso.3.6.1.4.1.7616.2.2.2 = INTEGER: 1 – Port3 link | + | iso.3.6.1.4.1.7616.2.3.2 = INTEGER: 10 – Port3 speed <br/> |
− | iso.3.6.1.4.1.7616.2.2.3 = INTEGER: 1 – Port4 link | + | iso.3.6.1.4.1.7616.2.3.3 = INTEGER: 10 – Port4 speed <br/> |
− | iso.3.6.1.4.1.7616.2.2.4 = INTEGER: 1 – Port5 link | + | iso.3.6.1.4.1.7616.2.3.4 = INTEGER: 1000 – Port5 speed <br/> |
− | iso.3.6.1.4.1.7616.2.3.0 = INTEGER: 10 – Port1 speed | + | iso.3.6.1.4.1.7616.2.4.0 = INTEGER: 0 – Port1 full/half duplex <br/> |
− | iso.3.6.1.4.1.7616.2.3.1 = INTEGER: 100 – Port2 speed | + | iso.3.6.1.4.1.7616.2.4.1 = INTEGER: 1 – Port2 full/half duplex <br/> |
− | iso.3.6.1.4.1.7616.2.3.2 = INTEGER: 10 – Port3 speed | + | iso.3.6.1.4.1.7616.2.4.2 = INTEGER: 0 – Port3 full/half duplex <br/> |
− | iso.3.6.1.4.1.7616.2.3.3 = INTEGER: 10 – Port4 speed | + | iso.3.6.1.4.1.7616.2.4.3 = INTEGER: 1 – Port4 full/half duplex <br/> |
− | iso.3.6.1.4.1.7616.2.3.4 = INTEGER: 1000 – Port5 speed | + | iso.3.6.1.4.1.7616.2.4.4 = INTEGER: 1 – Port5 full/half duplex <br/> |
− | iso.3.6.1.4.1.7616.2.4.0 = INTEGER: 0 – Port1 full/half duplex | + | iso.3.6.1.4.1.7616.2.5.0 = INTEGER: 0 – Port1 TX rate B/s <br/> |
− | iso.3.6.1.4.1.7616.2.4.1 = INTEGER: 1 – Port2 full/half duplex | + | iso.3.6.1.4.1.7616.2.5.1 = INTEGER: 2406 – Port2 TX rate B/s <br/> |
− | iso.3.6.1.4.1.7616.2.4.2 = INTEGER: 0 – Port3 full/half duplex | + | iso.3.6.1.4.1.7616.2.5.2 = INTEGER: 0 – Port3 TX rate B/s <br/> |
− | iso.3.6.1.4.1.7616.2.4.3 = INTEGER: 1 – Port4 full/half duplex | + | iso.3.6.1.4.1.7616.2.5.3 = INTEGER: 349 – Port4 TX rate B/s <br/> |
− | iso.3.6.1.4.1.7616.2.4.4 = INTEGER: 1 – Port5 full/half duplex | + | iso.3.6.1.4.1.7616.2.5.4 = INTEGER: 0 – Port5 TX rate B/s <br/> |
− | iso.3.6.1.4.1.7616.2.5.0 = INTEGER: 0 – Port1 TX rate B/s | + | iso.3.6.1.4.1.7616.2.6.0 = INTEGER: 0 – Port1 RX rate B/s <br/> |
− | iso.3.6.1.4.1.7616.2.5.1 = INTEGER: 2406 – Port2 TX rate B/s | + | iso.3.6.1.4.1.7616.2.6.1 = INTEGER: 2470 – Port2 RX rate B/s <br/> |
− | iso.3.6.1.4.1.7616.2.5.2 = INTEGER: 0 – Port3 TX rate B/s | + | iso.3.6.1.4.1.7616.2.6.2 = INTEGER: 0 – Port3 RX rate B/s <br/> |
− | iso.3.6.1.4.1.7616.2.5.3 = INTEGER: 349 – Port4 TX rate B/s | + | iso.3.6.1.4.1.7616.2.6.3 = INTEGER: 0 – Port4 RX rate B/s <br/> |
− | iso.3.6.1.4.1.7616.2.5.4 = INTEGER: 0 – Port5 TX rate B/s | + | iso.3.6.1.4.1.7616.2.6.4 = INTEGER: 0 – Port5 RX rate B/s <br/> |
− | iso.3.6.1.4.1.7616.2.6.0 = INTEGER: 0 – Port1 RX rate B/s | + | ===Grupa statusu portów=== |
− | iso.3.6.1.4.1.7616.2.6.1 = INTEGER: 2470 – Port2 RX rate B/s | + | |
− | iso.3.6.1.4.1.7616.2.6.2 = INTEGER: 0 – Port3 RX rate B/s | + | iso.3.6.1.4.1.7616.3.1.0 = INTEGER: 0 – Port1 Watchdog On/OFF <br/> |
− | iso.3.6.1.4.1.7616.2.6.3 = INTEGER: 0 – Port4 RX rate B/s | + | iso.3.6.1.4.1.7616.3.1.1 = INTEGER: 0 – Port2 Watchdog On/OFF <br/> |
− | iso.3.6.1.4.1.7616.2.6.4 = INTEGER: 0 – Port5 RX rate B/s | + | iso.3.6.1.4.1.7616.3.1.2 = INTEGER: 0 – Port3 Watchdog On/OFF <br/> |
− | Grupa statusu portów | + | iso.3.6.1.4.1.7616.3.1.3 = INTEGER: 0 – Port4 Watchdog On/OFF <br/> |
− | + | iso.3.6.1.4.1.7616.3.1.4 = INTEGER: 0 – OUT_T Watchdog On/OFF <br/> | |
− | + | iso.3.6.1.4.1.7616.3.2.0 = INTEGER: 0 – Port1 Watchdog email On/OFF <br/> | |
− | + | iso.3.6.1.4.1.7616.3.2.1 = INTEGER: 0 – Port2 Watchdog email On/OFF <br/> | |
− | iso.3.6.1.4.1.7616.3.1.0 = INTEGER: 0 – Port1 Watchdog On/OFF | + | iso.3.6.1.4.1.7616.3.2.2 = INTEGER: 1 – Port3 Watchdog email On/OFF <br/> |
− | iso.3.6.1.4.1.7616.3.1.1 = INTEGER: 0 – Port2 Watchdog On/OFF | + | iso.3.6.1.4.1.7616.3.2.3 = INTEGER: 1 – Port4 Watchdog email On/OFF <br/> |
− | iso.3.6.1.4.1.7616.3.1.2 = INTEGER: 0 – Port3 Watchdog On/OFF | + | iso.3.6.1.4.1.7616.3.2.4 = INTEGER: 0 – OUT_T Watchdog email On/OFF <br/> |
− | iso.3.6.1.4.1.7616.3.1.3 = INTEGER: 0 – Port4 Watchdog On/OFF | + | iso.3.6.1.4.1.7616.3.3.0 = INTEGER: 0 – Port1 Watchdog ping fail count <br/> |
− | iso.3.6.1.4.1.7616.3.1.4 = INTEGER: 0 – OUT_T Watchdog On/OFF | + | iso.3.6.1.4.1.7616.3.3.1 = INTEGER: 0 – Port2 Watchdog ping fail count <br/> |
− | iso.3.6.1.4.1.7616.3.2.0 = INTEGER: 0 – Port1 Watchdog email On/OFF | + | iso.3.6.1.4.1.7616.3.3.2 = INTEGER: 0 – Port3 Watchdog ping fail count <br/> |
− | iso.3.6.1.4.1.7616.3.2.1 = INTEGER: 0 – Port2 Watchdog email On/OFF | + | iso.3.6.1.4.1.7616.3.3.3 = INTEGER: 0 – Port4 Watchdog ping fail count <br/> |
− | iso.3.6.1.4.1.7616.3.2.2 = INTEGER: 1 – Port3 Watchdog email On/OFF | + | iso.3.6.1.4.1.7616.3.3.4 = INTEGER: 0 – OUT_T Watchdog ping fail count <br/> |
− | iso.3.6.1.4.1.7616.3.2.3 = INTEGER: 1 – Port4 Watchdog email On/OFF | + | iso.3.6.1.4.1.7616.3.4.0 = INTEGER: 0 – Port1 Watchdog restrat count <br/> |
− | iso.3.6.1.4.1.7616.3.2.4 = INTEGER: 0 – OUT_T Watchdog email On/OFF | + | iso.3.6.1.4.1.7616.3.4.1 = INTEGER: 0 – Port2 Watchdog restrat count <br/> |
− | iso.3.6.1.4.1.7616.3.3.0 = INTEGER: 0 – Port1 Watchdog ping fail count | + | iso.3.6.1.4.1.7616.3.4.2 = INTEGER: 0 – Port3 Watchdog restart count <br/> |
− | iso.3.6.1.4.1.7616.3.3.1 = INTEGER: 0 – Port2 Watchdog ping fail count | + | iso.3.6.1.4.1.7616.3.4.3 = INTEGER: 0 – Port4 Watchdog restart count <br/> |
− | iso.3.6.1.4.1.7616.3.3.2 = INTEGER: 0 – Port3 Watchdog ping fail count | + | iso.3.6.1.4.1.7616.3.4.4 = INTEGER: 0 – OUT_T Watchdog restart count <br/> |
− | iso.3.6.1.4.1.7616.3.3.3 = INTEGER: 0 – Port4 Watchdog ping fail count | + | ===Grupa watchdog=== |
− | iso.3.6.1.4.1.7616.3.3.4 = INTEGER: 0 – OUT_T Watchdog ping fail count | + | |
− | iso.3.6.1.4.1.7616.3.4.0 = INTEGER: 0 – Port1 Watchdog restrat count | + | |
− | iso.3.6.1.4.1.7616.3.4.1 = INTEGER: 0 – Port2 Watchdog restrat count | ||
− | iso.3.6.1.4.1.7616.3.4.2 = INTEGER: 0 – Port3 Watchdog restart count | ||
− | iso.3.6.1.4.1.7616.3.4.3 = INTEGER: 0 – Port4 Watchdog restart count | ||
− | iso.3.6.1.4.1.7616.3.4.4 = INTEGER: 0 – OUT_T Watchdog restart count | ||
− | Grupa watchdog | ||
− | |||
− | |||
− | |||
− | |||
− | |||
www.tinycontrol.eu | www.tinycontrol.eu | ||
Konsorcjum ATS Sp.J. | Konsorcjum ATS Sp.J. |
Aktualna wersja na dzień 11:21, 24 mar 2017
Managed PoE switch is unique device designed as combination of management switch, PoE injector and in/out controller. In opposite to typical PoE switches this one don't has fixed voltage output. This parameter depend on voltage of connected supply. Thanks it switch is very universal and what is very important power supply uninterruptible is very easy to implementation. Just need to connect buffered uninterruptible power supply with battery (also in offer in our shop). This solution allow for much higher possible output current, limited to 2A per port. It is important for momentary spikes of current, often occurring during start up. However should be remember that high current can damage RJ45 connectors quick - they are not designed for this applications. All supply parameters can be monitored online, also ICMP packets returns is monitored by watchdog, if ping don't reply, output can be reseted. Switch characterised by unique design - it is only 31mm deep and 1U high. So could be installed in typical 10" rack cabinets as well as in very flat, small cabinets for example on corridors. Other useful feature are 2 logical inputs for monitoring switch surrounds (for ex cabinet doors) and one voltage output (up to 1A) to remote power different devices. In addition PoeSwitch 4F1G have reset button.
Spis treści
Manual
4F1G Switch 4 ports 10/100Mb PoE + 1 port 1Gb aktual: HW:2.1 SW:1.06
Managed PoE switch is unique device designed as combination of management switch, PoE injector and in/out controller.
In opposite to typical PoE switches this one don’t has fixed voltage output. This parameter depend on voltage of connected supply. Thanks it switch is very universal and what is very important power supply uninterruptible is very easy to implementation. Just need to connect buffered uninterruptible power supply with battery (also in offer in our shop). This solution allow for much higher possible output current, limited to 2A per port. It is important for momentary spikes of current, often occurring during start up. However should be remember that high current can damage RJ45 connectors quick - they are not designed for this applications. All supply parameters can be monitored online, also ICMP packets returns is monitored by watchdog, if ping don’t reply, output can be reseted. Switch characterised by unique design - it is only 31mm deep and 1U high. So could be installed in typical 10” rack as well as in very flat, small cabinets for example on corridors. Other useful feature are 2 logical inputs for monitoring switch surrounds (for ex cabinet doors) and one voltage output (up to 1A) to remote power different devices.
MAIN FEATURES:
- management by WWW or SNMP v2. (all SNMP features available after upgrade)
- firmware upgrade remotely by TFTP
- read data in real time without refresh the page
- ON/OFF power to four passive PoE ports directly from a web page or SNMP
- Watchdog IP on all ports (email notification, trap, reset of power on PoE)
- 1 analog measure input
- 2 logical inputs
- environment temperature measurement
- voltage measurement: resolution, accuracy ± 0.1 V
- current measurement on each port and consumed by all
- date and time from NTP or manual
- email alert when Watchdog activation
- automatic sending of SNMP TRAP (VCC, temperature, INPD, INPA)
- supported protocols: HTTP, SNMP, SMTP, NTP, ICMP, DNS, DHCP.
- 4 ports 100/10Mbit
- 1 port 1Gbit
- limit power on the PoE port when 2A current is exceeded.
- VLAN support
- optional mounting on DIN rail
TECHNICAL SPECIFICATIONS
- power supply voltage: 9÷53V
- current consumption at one POE port: 2A (recommended for ling life 1A)
- total power on all ports: ≤ 6A
- power consumption of the switch: <1W
- protection against reverse polarity: YES
- maximal current from transistor output: 1A
- work temperature: –20 do +85 °C
- weight: 0,350kg
- housing high: 1U
- housing sizes without holders: 146 (173 with holders) x 45 x 31 mm
PORTS AND COMPONENTS
POWER – power over plug DC5,5 / 2.1 or terminal block LED PoE – LED orange, shining denotes activating the power per port PoE LED LINK – LED green lights means the active link, blinking - data transfer RX / TX INP1D, INP2D –digital inputs for monitoring, eg. power supply buffer, max input voltage 24V. OUT_T – voltage output transistor performance 1A. The voltage represents switch power supply voltage. INP1A – analog input for voltage measurement in the range 0÷3,3V Default user and password is „admin” IP adress is 192.168.1.200 POWER OUT_T LED PoE LED LINK INP1D INP2D INP1A 4 4F1G Switch - HW:2.1 SW:1.06 – POESWG-030 www.tinycontrol.eu Management by WWW.
STATUS
In this window is a summary presented the switch current status. PoE on/off – specifies the state of power supply on PoE port: green ON, a red OFF. PoE [mA] – shows the current consumption of the device. PoE [W] – shows the power consumption of the device. INP1A [V] – shows the voltage at the input INP1A. INP1D State – shows the status of the input INP1D. INP2D State – shows the status of the input INP2D. Out_T on/off – shows the status of output Out_T.
POE
zdjecie
PORTS
any description max 8 characters The value in seconds to return to the OFF state after switching PoE POWER ON The value of the current drawn by the device per port PoE PoE POWER ON/OFF selection switches Power on the PoE port after reboot / start switch
VLAN
Inclusion of of isolation between ports: In order to isolate traffic between the ports, so that the traffic was directed only to the individual ports 1÷4, for example, only port Gigabit P5 you can use the Port based VLAN Member. For the example above, only the ports select „M” (if we are able to manage the switch from each port) and port „5”. For the port „5” we leave all selections (except P5). Then memorize the setting with „Save” button.
WATCHDOG
Email send – sends an e-mail when the watchdog work (will restart power supply on a port PoE). E-mail contains information about the number of the current restart and a maximum permissible number of restarts and time of occurrence. ICMP time – it shows in milliseconds latency response to an ICMP packet. ICMP fail – number of unanswered response to a query ICMP, followed by a triggering of the watchdog. ICMP wait time – response time in seconds. ICMP send period – the period of time in seconds between successive queries ICMP. Wait time after restart – the period of time in seconds before sending another query ICMP after activation of the watchdog. Restart time – the period of time in seconds for how long it will turn off the power at the port PoE after activation of the watchdog. Max restart – maksymalna liczba restartów (zadziałań watchdoga). Gdy ta liczba zostanie osiągniętą watchdog na danym porcie zostanie wyłączony, żeby w nieskończoność nie restartować urządzenia, które i tak nie ma zamiaru poprawnie pracować. POE state – determines the state of power supply to PoE port: red OFF, green ON.
SWITCH SETTINGS
The user name and password to access the module. You can disable authorization. NTP Server Settings, Time Interval - time in minutes, at what time will be synchronized with the server. network settings configuration.
Configure email account to send notifications. Bootloader start – toggles the switch in software upgrade mode Password for SNMP
Software update
In the event that there is a new version of the software it is possible to load such software for the device.
To install the new firmware to the switch should move it in bootloader mode. The easiest way to do it from the menu Switch Settings/Others:
1. the „Upgrade Enabled” in the Switch Settings / Access must be enabled. 2. through the „Bootloader start” button. We have 60 seconds to start uploading via FTP. This will take about 6÷7 seconds and after this time, the switch will reboot automatically. If at uploading was a mistake, bootlaoder mode will automatically restart until the correct upload file. Bootloader start – toggles the switch in software upgrade mode Upgrade Enabled – It must be enabled to allow the upload new software Contents of the instructions is regularly checked and if necessary corrected. If the observations errors or inaccuracies, please contact us. It can not be ruled out that, despite best efforts, however, some discrepancies arose. To get the latest version, please contact us or distributors. © Konsorcjum ATS Sp.J. Copying, duplication, reproduction whole or in part without the consent of the owner is prohibited.
SNMP OID NUMBERS
A group of voltages, currents, inputs, PoE
iso.3.6.1.4.1.7616.1.1.0 = INTEGER: 125 – supply voltage, divide the result by 10
iso.3.6.1.4.1.7616.1.1.1 = INTEGER: 0 – INP1A, voltage, divide the result by 10
iso.3.6.1.4.1.7616.1.1.2 = INTEGER: 387 – temperature, divide the result by 10
iso.3.6.1.4.1.7616.1.1.3 = INTEGER: 1 – INP1D
iso.3.6.1.4.1.7616.1.1.4 = INTEGER: 1 – INP2D
iso.3.6.1.4.1.7616.1.2.0 = INTEGER: 1 – PoE port1 ON/OFF
iso.3.6.1.4.1.7616.1.2.1 = INTEGER: 1 – PoE port2 ON/OFF
iso.3.6.1.4.1.7616.1.2.2 = INTEGER: 1 – PoE port3 ON/OFF
iso.3.6.1.4.1.7616.1.2.3 = INTEGER: 1 – PoE port4 ON/OFF
iso.3.6.1.4.1.7616.1.2.4 = INTEGER: 0 – PoE OUT_T ON/OFF
iso.3.6.1.4.1.7616.1.3.0 = INTEGER: 0 – PoE port1 current mA
iso.3.6.1.4.1.7616.1.3.1 = INTEGER: 21 – PoE port2 current mA
iso.3.6.1.4.1.7616.1.3.2 = INTEGER: 53 – PoE port3 current mA
iso.3.6.1.4.1.7616.1.3.3 = INTEGER: 0 – PoE port4 current mA
iso.3.6.1.4.1.7616.1.3.4 = INTEGER: 74 – PoE the sum of currents from p1 to p4 mA
iso.3.6.1.4.1.7616.1.4.0 = INTEGER: 0 – PoE port1 power mW
iso.3.6.1.4.1.7616.1.4.1 = INTEGER: 262 – PoE port2 power mW
iso.3.6.1.4.1.7616.1.4.2 = INTEGER: 662 – PoE port3 power mW
iso.3.6.1.4.1.7616.1.4.3 = INTEGER: 0 – PoE port4 power mW
iso.3.6.1.4.1.7616.1.4.4 = INTEGER: 925 – PoE the sum of power from p1 to p4 mW
iso.3.6.1.4.1.7616.2.1.0 = INTEGER: 1 – Port1 On/OFF
iso.3.6.1.4.1.7616.2.1.1 = INTEGER: 1 – Port2 On/OFF
iso.3.6.1.4.1.7616.2.1.2 = INTEGER: 1 – Port3 On/OFF
iso.3.6.1.4.1.7616.2.1.3 = INTEGER: 1 – Port4 On/OFF
iso.3.6.1.4.1.7616.2.1.4 = INTEGER: 1 – Port5 On/OFF
iso.3.6.1.4.1.7616.2.2.0 = INTEGER: 0 – Port1 link
iso.3.6.1.4.1.7616.2.2.1 = INTEGER: 1 – Port2 link
iso.3.6.1.4.1.7616.2.2.2 = INTEGER: 1 – Port3 link
iso.3.6.1.4.1.7616.2.2.3 = INTEGER: 1 – Port4 link
iso.3.6.1.4.1.7616.2.2.4 = INTEGER: 1 – Port5 link
iso.3.6.1.4.1.7616.2.3.0 = INTEGER: 10 – Port1 speed
iso.3.6.1.4.1.7616.2.3.1 = INTEGER: 100 – Port2 speed
iso.3.6.1.4.1.7616.2.3.2 = INTEGER: 10 – Port3 speed
iso.3.6.1.4.1.7616.2.3.3 = INTEGER: 10 – Port4 speed
iso.3.6.1.4.1.7616.2.3.4 = INTEGER: 1000 – Port5 speed
iso.3.6.1.4.1.7616.2.4.0 = INTEGER: 0 – Port1 full/half duplex
iso.3.6.1.4.1.7616.2.4.1 = INTEGER: 1 – Port2 full/half duplex
iso.3.6.1.4.1.7616.2.4.2 = INTEGER: 0 – Port3 full/half duplex
iso.3.6.1.4.1.7616.2.4.3 = INTEGER: 1 – Port4 full/half duplex
iso.3.6.1.4.1.7616.2.4.4 = INTEGER: 1 – Port5 full/half duplex
iso.3.6.1.4.1.7616.2.5.0 = INTEGER: 0 – Port1 TX rate B/s
iso.3.6.1.4.1.7616.2.5.1 = INTEGER: 2406 – Port2 TX rate B/s
iso.3.6.1.4.1.7616.2.5.2 = INTEGER: 0 – Port3 TX rate B/s
iso.3.6.1.4.1.7616.2.5.3 = INTEGER: 349 – Port4 TX rate B/s
iso.3.6.1.4.1.7616.2.5.4 = INTEGER: 0 – Port5 TX rate B/s
iso.3.6.1.4.1.7616.2.6.0 = INTEGER: 0 – Port1 RX rate B/s
iso.3.6.1.4.1.7616.2.6.1 = INTEGER: 2470 – Port2 RX rate B/s
iso.3.6.1.4.1.7616.2.6.2 = INTEGER: 0 – Port3 RX rate B/s
iso.3.6.1.4.1.7616.2.6.3 = INTEGER: 0 – Port4 RX rate B/s
iso.3.6.1.4.1.7616.2.6.4 = INTEGER: 0 – Port5 RX rate B/s
Grupa statusu portów
iso.3.6.1.4.1.7616.3.1.0 = INTEGER: 0 – Port1 Watchdog On/OFF
iso.3.6.1.4.1.7616.3.1.1 = INTEGER: 0 – Port2 Watchdog On/OFF
iso.3.6.1.4.1.7616.3.1.2 = INTEGER: 0 – Port3 Watchdog On/OFF
iso.3.6.1.4.1.7616.3.1.3 = INTEGER: 0 – Port4 Watchdog On/OFF
iso.3.6.1.4.1.7616.3.1.4 = INTEGER: 0 – OUT_T Watchdog On/OFF
iso.3.6.1.4.1.7616.3.2.0 = INTEGER: 0 – Port1 Watchdog email On/OFF
iso.3.6.1.4.1.7616.3.2.1 = INTEGER: 0 – Port2 Watchdog email On/OFF
iso.3.6.1.4.1.7616.3.2.2 = INTEGER: 1 – Port3 Watchdog email On/OFF
iso.3.6.1.4.1.7616.3.2.3 = INTEGER: 1 – Port4 Watchdog email On/OFF
iso.3.6.1.4.1.7616.3.2.4 = INTEGER: 0 – OUT_T Watchdog email On/OFF
iso.3.6.1.4.1.7616.3.3.0 = INTEGER: 0 – Port1 Watchdog ping fail count
iso.3.6.1.4.1.7616.3.3.1 = INTEGER: 0 – Port2 Watchdog ping fail count
iso.3.6.1.4.1.7616.3.3.2 = INTEGER: 0 – Port3 Watchdog ping fail count
iso.3.6.1.4.1.7616.3.3.3 = INTEGER: 0 – Port4 Watchdog ping fail count
iso.3.6.1.4.1.7616.3.3.4 = INTEGER: 0 – OUT_T Watchdog ping fail count
iso.3.6.1.4.1.7616.3.4.0 = INTEGER: 0 – Port1 Watchdog restrat count
iso.3.6.1.4.1.7616.3.4.1 = INTEGER: 0 – Port2 Watchdog restrat count
iso.3.6.1.4.1.7616.3.4.2 = INTEGER: 0 – Port3 Watchdog restart count
iso.3.6.1.4.1.7616.3.4.3 = INTEGER: 0 – Port4 Watchdog restart count
iso.3.6.1.4.1.7616.3.4.4 = INTEGER: 0 – OUT_T Watchdog restart count